Permit: T05PL01690

Parcel: 13811055F


Addresses:

6410 S FONTANA AV


Inspection Status: Partial Approval

Inspection History: PLUMBING - YARD WTR LINE/TEST

Permit Number - T05PL01690

Inspection Description - PLUMBING - YARD WTR LINE/TEST

Inspection Status - Partial Approval

Date Description Inspector Results Comments
03/14/2006 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
OK TO COVER
CALL FOR FINAL APPROVAL AFTER ADDRESSING
SIZE OR RP
03/09/2006 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
1184/11676/31 -- PROVIDE 12' OF COVER IN THESE AREAS.
AT UNIT 31 PROVIDE FULL SIZE TEE THAN REDUCE TO 1"
REDLINE PLANS TO REFLECT CHANGE IN SIZE FOR BRANCH SERVING #'S 28-32
OK TO COVER ALL EXCEPT BRANCHES TO 1184, 11676 AND 31
CORRECTIONS AT WELL AND RP PIPING OK
03/06/2006 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
03/02/2006 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
TRACER WIRE INSTALLED ON NORTHERN EAST/WEST PIPING RUN. OK TO COVER PIPING ON NORTHERN EAST/WEST PIPING RUN.
APPROVED PLAN SHOWS AN EXISTING 3" RP, BUT THE RP IS ONLY 2". REVISE PLAN TO SHOW CORRECT PIPING SIZE
02/28/2006 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
INSTALL BLUE TRACER WIRE IN DITCH, ATTACH TO PIPE
REMOVE PVC FEMALE FITTINGS AT WELL AND RP LOCATION
OK TO COVER PIPING UNDER ASPHALT ROADWAY
WILL NEED TO SEE TRACER WIRE INSTALLED ON ALL PIPING
RECALL FOR INSPECTION.