Permit: T05PL01591

Parcel: 116201350


Addresses:

471 W CONGRESS ST


Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - FINAL

Permit Number - T05PL01591

Inspection Description - PLUMBING - FINAL

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
02/22/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
RECEIVED (1) BACKFLOW CERTIFICATIN FOR SUPPLY TO HOSE REELS. RECEIVED (1) LETTER FROM PROFESSIONAL ENGINEERING & TECHNOLOGY GIVING OK FOR SPR35 MATERIAL TYPE FOR SEWER AND WATER PIPING TO FLUSH HOPPERS.
THERE HAS BEEN NO CHANGE ON WORK COVERED WITHOUT INSPECTION. UNABLE TO OBTAIN PROOF OF SITE SEWER INSPECTION. UNABLE TO LOCATE CLEANOUTS THAT WOULD BE REQUIRED AT 100' INTERVALS ON SITE SEWER. BUILDING IS OCCUPIED WITHOUT INSPECTION APPROVAL
02/17/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PLEASE SEE NOTES FROM 2/8/06 INSPECTION #1, #2, #4 PROVIDE THEM. SITE SEWER HAS BEEN COVERED WITHOUT INSPECTION. POSSIBLE APPEAL TO BUILDING OFFICIAL COULD RESOLVE THIS ISSUE.
02/08/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PROVIDE PROOF OF INSPECTION WITH TEST ON 4" SITE SEWER. SDR 35 IS INSTALLED PLAN SPEC CALLS FOR PVC SCH 40 PLEASE PROVIDE STAMPED LETTER FROM ENGINEER OR ARCH. GIVING OK FOR THIS MATERIAL.
2. WATER PIPING IS NOT INSTALLED PER PLAN, PLEASE PROVIDE CITY APPROVED REVISED PLAN OF WATER INSTALLATION. FOR SIZING SUPPLY PIPING IS UNDERSIZED FROM POINT OF CONNECTION AT EXISTING AND TAILPIECE IS UNDER SIZED TO HOPPERS. PLAN SPEC ALSO CALLS FOR INSULATION ON UNDERGROUND WATER PIPING PROVIDE LETTER FROM ENGINEER OR ARCH DELEATING THIS INSULATION.
3. HOSE REELS SHALL REQUIRE VACUUM BREAKERS AND SIGNAGE FOR NON-POTABLE WATER DO NOT DRINK.
4. PROVIDE BACKFLOW CERTIFICATION ON MAIN DEVICE.
5. PROVIDE TRACER WIRE PER HOUSE BILL 2256
WATER TEST FOR (2) FLUSH HOPPERS FROM CONNECTION AT 4" SPR 2' FROM HOPPER AND (2) 3" VENTS TO 4" VENT 10' ABOVE FINISH GRADE (0K) -- WATER PIPING FROM 2' UNDERGROUND AT MANIFOLD FOR FLUSH VALVES 1" TO (2) FLUSH HOPPERS OK PENDING CITY APPROVED REVISED PLAN
COVER AT OWN RISK.
12/19/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*YOU MUST POST YOUR ADDRESS
NOT READY FOR INSPECTION
WORK COVERED WITHOUT INSPECTION IE,COPPER UNDERGROUND NOT SLEEVED MAT'L TYPE?
PLEASE SCHEDULE AM INSPECTION SO WE CAN GET YOU UP TO DATE. JASON 909 5147
STEVE 954 0157