Permit: T05PL01591

Parcel: 116201350


Addresses:

471 W CONGRESS ST


Inspection Status: Partial Approval

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T05PL01591

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
02/08/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
12/21/2005 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1. WHERE IS THE ADDRESS POSTED? YOU'VE BEEN ASKED MORE THAN ONCE PLEASE POST YOUR ADDRESS!!!!
2. SPOKE WITH TRINI ON 10/07/05 SAW ONLY THE HCS CONNECTION - UNDERGROUND INSTALLED AND COVERED WITHOUT INSPECTION. UNABLE TO LOCATE VENTS FOR HOPPERS. COPPER DIRECTLY EMBEDDED IN CONCRETE. NO INSULATION ON UNDERGROUND.
3. PROVIDE ACCURATE REDLINES.
4. PROVIDE DETAIL FOR HOPPERS.
10/07/2005 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :* 4" SDR 35 INSTALLED PER REDLINES OK.
WATER TEST OK
HCS CONNECTION INSPECTED BY OTHERS
OK TO COVER