Permit: T05PL01559

Parcel: 10706014G

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T05PL01559

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/06/2005 PLUMBING - FINAL Approved IVRS - Inspection :*CORRECTIONS MADE OK. OK FOR GAS. CARD LEFT AT METER.
10/05/2005 PLUMBING - FINAL Cancelled IVRS - RI canceled
10/03/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :* THE ABOVE GRADE PIPING UNDER THE TRAILER DOES NOT NEED TO BE VENTED.
THE UNDERGROUND PIPING UNDER THE PORCH IS THE SECTION THAT NEEDS TO BE SLEEVED AND VENTED.
VENTING MAY NOT TERMINATE BELOW GRADE
EIGHTEEN INCHES BELOW GRADE IS AT ALL POINTS
09/29/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) GAS PIPING BURIED IN A MOBILE HOME PARK TO BE A MINIMUM OF EIGHTEEN INCHES DEEP
2) GAS PIPE MAY NOT BE BURIED UNDER ANY MOBILE HOME. THE PORCH IS PART OF THE MOBILE HOME
3) ALL SECTIONS OF PIPE MARRED BY WRENCHES TO BE WRAPPED
4) I DIDN'T SEE ANY SUPPORT ON THE GAS LINE UNDER THE MOBILE HOME
5) INSPECTION STOPPED