Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T05PL01559
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :*CORRECTIONS MADE OK. OK FOR GAS. CARD LEFT AT METER. | |
| 10/05/2005 | PLUMBING - FINAL | Cancelled | IVRS - RI canceled | |
| 10/03/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* THE ABOVE GRADE PIPING UNDER THE TRAILER DOES NOT NEED TO BE VENTED. THE UNDERGROUND PIPING UNDER THE PORCH IS THE SECTION THAT NEEDS TO BE SLEEVED AND VENTED. VENTING MAY NOT TERMINATE BELOW GRADE EIGHTEEN INCHES BELOW GRADE IS AT ALL POINTS |
|
| 09/29/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) GAS PIPING BURIED IN A MOBILE HOME PARK TO BE A MINIMUM OF EIGHTEEN INCHES DEEP 2) GAS PIPE MAY NOT BE BURIED UNDER ANY MOBILE HOME. THE PORCH IS PART OF THE MOBILE HOME 3) ALL SECTIONS OF PIPE MARRED BY WRENCHES TO BE WRAPPED 4) I DIDN'T SEE ANY SUPPORT ON THE GAS LINE UNDER THE MOBILE HOME 5) INSPECTION STOPPED |