Permit: T05PL01550

Parcel: 125111660


Addresses:

814 N DODGE BL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
09/30/2005 PLUMBING - FINAL Approved IVRS - Inspection :* 15 PSI FROM METER OVERHEAD TO WATER HEATER & FURNACE OK CORRECTION MAKE GAS CARD AT METER
09/28/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* DO NOT PAINT PIPING UNTIL IT IS VIEWED FOR CORRECT TYPE.
SECURE PIPNG AT METER LOCATION
GAS PIPING CANNOT BLOCK WATER HEATER PULL SPACE
SECURE GAS PIPING IN FURNACE WATER HEATER CLOSET
PROVIDE BONDING OF BUILDING GAS PIPING
VENT FROM WATER HEATER & FURNACE TO BE 3' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF COOLER INTAKE.
PROVIDE PERMIT FOR WATER HEATER
WATER HEATER TEMPERATURE & PRESSURE RELIEF DRAIN PIPING TO BE FULL SIZE GRAVITY DRAIN TO DAYLIGHT
DRAFT SPACE BETWEEN SINGLE & DOUBLE WALL VENT CONNECTION TO BE FREE OF TAPE.