Permit: T05PL01470

Parcel: 136073500


Addresses:

9359 E 30TH ST

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/06/2005 PLUMBING - FINAL Denied SEE NOTE #2 FROM 9/20/05 NOT READY
10/04/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*SEE NOTE #2 FROM 9.20/05 INSPECTION AND PROVIDE 3 GALV SCREWS AT EACH JOINT OF WATER HEATER VENT PIPING
09/27/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WATER HEATER SEE NOTE #2 FROM 9/20/05 INSPECTION. NO FLEX SHALL BE USED
09/20/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE BONDING OF BUILDING GAS PIPING
2) WATER HAETER TEMPERATURE AND PRESSURE RELIEF DRAIN PIPING TO BE FULL SIZE GRAVITY DRAIN TO DAYLIGHT. WITH APPROVED PIPING MATERIALS