Permit: T05PL01470

Parcel: 136073500


Addresses:

9359 E 30TH ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
10/06/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*16 PSI AIR TEST FROM METER OVERHEAD TO WATER HEATER & FURNACE ONLY OK. GAS CARD AT METER.
10/04/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*SEE NOTE FROM 9/20/05 TEST SHALL HOLD FOR 15 MIN WITH NO PRESSURE DROP
09/27/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TO BE FULL SIZE GRAVITY DRAIN TO DAYLIGHT WITH APPROVED PIPING MATERIALS
2) TEST AT 8.5 ON ARRIVAL TEST AT 8.3 15 MINUTES LATER. PLEASE PROVIDE MINIMUM 10 PSI AT NEXT INSPECTION
09/20/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
10 PSI TEST SHALL HOLD FOR 15 MINUTES WITH NO PRESSURE LOSS