Permit: T05PL01468

Parcel: 128061850


Addresses:

6039 E BEVERLY ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
09/22/2005 PLUMBING - FINAL Approved IVRS - Inspection :*
PETITION OF APPEAL #2005.253 OK SITE. CORRECTION MADE GAS CARD AT METER
CALL S.W. GAS 889-1888 TO ENERGIZE GAS SYSTEM
09/19/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CORRECT ELECTRICAL WIRING BLOCKING WATER HEATER PULL SPACE. PROVIDE RIGID PIPE NIPPLE THRU FURNACE APPLIANCE HOUSING
2) PROVIDE LISTED FLEX FOR BTU REQUIREMENT OF FURNACE
3) WATER HEATER REQUIRES TEMPERATURE AND PRESSURE RELIEF DRAIN PIPING TO GRAVITY DRAIN TO DAYLIGHT OR PROVIDE CITY SIGNED PETITION OF APPEAL ON SITE WITH CORRECT INSTALLATION
4) SINGLE WALL VENT FROM WATER HEATER REQUIRES 6" MINIMUM CLEARANCE FROM COMBUSTABLES. DOUBLE WALL REQUIRES 1" CLEARANCE FROM COMBUSTABLES
5) GAS VENT APPLIANCES TERMINATE WITHIN 10' OF COOLER INTAKE REQUIRES VENT TERMINATION OF WATER HEATER TO BE 3' ABOVE, FURNACE TO BE 2' ABOVE TOP OF COOLER INTAKE
6) PROVIDE COMBUSTION AIR REQUIREMENTS FOR WATER HEATER