Permit: T05PL01455

Parcel: 117082690


Addresses:

910 S 3RD AV #05

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
10/03/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
09/30/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999* SEE NOTE FROM 9/26/05 GAUGE TO BE IN WORKING ORDER
09/26/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999* THIS IS NOT A RECONNECT. 1. PROVIDE WORKING GAS TEST GAUGE. MINIMUM 10 PSI TEST SHALL HOLD PRESSURE FOR 15 MINUTES WITH NO PRESSURE DROP. 2. PROVIDE PERMIT FOR ROOF TOP HEATING & A/C UNIT. 3. PROVIDE BONDING OF BUILDING GAS PIPING. 4. SUPPORT ROOF TOP GAS PIPING AT 1ST 90 DEGREE CHANGE OF DIRECTION ON ROOF.
09/23/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :* 9:30 PLEASE HAVE AN ADULT PRESENT TO PROVIDE ACCESS TO ENTIRE GAS SYSTEM AT TIME OF REINSPECTION.