Permit: T05PL01422

Parcel: 138080710

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/20/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* PROVIDE AGA OR CSA APPROVED GAS VALVES AT ALL APPLIANCES
PROVIDE 10"X10" MINIMUM OF 100 SQ INCHES UPPER & LOWER COMBUSTION AIR OPENINGS WITH LOUVERS AT WATER HEATER FURNACE AREA.
PROVIDE BONDING OF BLDG GAS PIPING.
VENT FROM FURNACE TO TRAVEL IN UPWARD DIRECTION TO POINT OF TERMINATION.
VENT FROM WATER HEATER/FURNACE TO HAVE 3- GALV. SCREWS AT EACH JOINT AND BE 3' ABOVE TOP OF COOLER INTAKE WITH DOUBLE WALL VENT PIPING & APPROVED CAP