Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/20/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE AGA OR CSA APPROVED GAS VALVES AT ALL APPLIANCES PROVIDE 10"X10" MINIMUM OF 100 SQ INCHES UPPER & LOWER COMBUSTION AIR OPENINGS WITH LOUVERS AT WATER HEATER FURNACE AREA. PROVIDE BONDING OF BLDG GAS PIPING. VENT FROM FURNACE TO TRAVEL IN UPWARD DIRECTION TO POINT OF TERMINATION. VENT FROM WATER HEATER/FURNACE TO HAVE 3- GALV. SCREWS AT EACH JOINT AND BE 3' ABOVE TOP OF COOLER INTAKE WITH DOUBLE WALL VENT PIPING & APPROVED CAP |