Permit: T05PL01420

Parcel: 136282980

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
09/08/2005 PLUMBING - FINAL Approved IVRS - Inspection :*
1) 13 PSI AIR TEST FROM NEW METER LOCATION ABOVE GROUND TO EXISTING SERVICE ENTRANCE TO STOVE, WATER HEATER AND FURNACE OK
2) CORRECTION MADE
09/07/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) SINGLE WALL VENT PIPING REQUIRES 6" MINIMUM CLEARANCE FROM COMBUSTIBLES FOR FURNACE
2) REMOVE TAPE AT DRAFT SPACE AT SINGLE TO DBL WALL VENT CONNECTION
3) PROVIDE APPROVED VENT CAP FOR FURNACE WATER HEATER TERMINATING 2' FROM FURNACE 3' FOR WATER HEATER ABOVE AIR INTAKE FOR COMBUSTION AIR
4) PROVIDE GOOD CONNECTION FOR BONDING CLAMPS (REMOVE PAINT) OR CLEAN PIPING