Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/06/2005 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* 1) ALL CORRECTIONS HAVE BEEN MADE 2) OK FOR DRYWALL |
|
| 09/02/2005 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHALL PROVIDE A 1 1/2" TRAP ARM MAX SIZE FOR LAVATORY |
|
| 09/01/2005 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CAN'T POSITION A COMBO IN A VERTICAL POSITION. THIS WILL PUT THE VENT OUTLET BELOW THE TRAP 2) SHALL PROVIDE 1 1/2" TRAP ARM ALL THE WAY TO THE BARREL USE A 4 X 1 1/2" SAN TEE 3) SHALL PROVIDE A L-SWEEP ON HORIZONTAL TO HORIZONTAL DRAINAGE AT TRAP ARM 4) SHALL REMOVE TEST TEE AND CONNECT SOLID. NO ABS THREADED FITTING CAN BE LOCATED IN A CONSEALED LOCATION. FLOW TEST OK 5) SHALL PROVIDE APPROVED SPECIALTY COUPLING WHEN CONNECTING DISSIMULAR MATERIAL |