Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T05PL01388
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/01/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 15 PSI TEST IS OK LEFT GAS CARD PROVIDE A 125 PSI RELIEF VALVE OUTSIDE ON WATER SUPPLY PROVIDE A BOND JUMPER WILL CHECK CORRECTIONS ON MECHANICAL INSPECTION |
|
08/29/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE PERMITS FOR WATER HEATER AND ROOF TOP UNIT 2) PROVIDE CITY APPROVED GAS ISOMETRIC OF YOUR GAS SYSTEM AND HAVE INTERMEDIATE PLUMBING INSPECTION ADDDED ON A PERMIT FOR REWORK OF WATER HEATER PIPING AND EXPOSE THIS WORK 3) RINNAI WATER HEATRS REQUIRE CERTIFIED INSTALLERS PROVIDE CERTIFICATION ON SITE HEATER ALSO REQUIRES VENT THR ROOF AND COMBUSTION AIR INTAKE 4) ALL GAS APPLIANCES TO HAVE SHUT OFF VALVES WITHIN 3' OF APPLIANCE IN SAME SPACE 5) WATER HEATER T & P TO GRAVITY DRAIN TO DAY LIGHT 6) SECURE ALL GAS PIPING PROPERLY 7) WATER HEATER TO BE VALVED AND HAVE UNIONS ON INLETS |