Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/27/2005 PLUMBING - FINAL Approved IVRS - Inspection :*FINAL CONNECTION TO FOOT SPAS ARE OK
BACKFLOW PREVENTER TEST & CERT HAVE BEEN DONE.
10/25/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*SOIL WATER TEST IS OK
OVERHEAD WATER DISTRIBUTION IS OK
P.O,C OF NEW BLDG DRAIN TO EXISTING BLDG. DRAIN IS OK
NOTE: SHALL SEE FINAL CONNECTION TO FOOT SPAS AND WATER SUPPLY AND HAVE TEST & CERTIFICATION RESULTS @ TIME OF FINAL INSPECTION.
10/21/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*SHALL PROVIDE A MIN TRAP ARM DISTANCE FOR EACH P-TRAP. THIS DISTANCE IS 2 X THE PIPE SIZE FROM THE BARREL OF THE VENT TO WIER OF THE TRAP.
SHALL CONNECT 2" DRAIN TO LAVATORY VERTICAL DRAIN AS PER PLAN
SHALL PROVIDE TEST & CERTIFICATIONS FOR ALL BACKFLOW PREVENTERS
RE TEST THE SYSTEM
SHALL PERM CAP WATER CLOSET VENT @ SAN TEE.