Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T05PL01366
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/27/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :*FINAL CONNECTION TO FOOT SPAS ARE OK BACKFLOW PREVENTER TEST & CERT HAVE BEEN DONE. |
|
10/25/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*SOIL WATER TEST IS OK OVERHEAD WATER DISTRIBUTION IS OK P.O,C OF NEW BLDG DRAIN TO EXISTING BLDG. DRAIN IS OK NOTE: SHALL SEE FINAL CONNECTION TO FOOT SPAS AND WATER SUPPLY AND HAVE TEST & CERTIFICATION RESULTS @ TIME OF FINAL INSPECTION. |
|
10/21/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*SHALL PROVIDE A MIN TRAP ARM DISTANCE FOR EACH P-TRAP. THIS DISTANCE IS 2 X THE PIPE SIZE FROM THE BARREL OF THE VENT TO WIER OF THE TRAP. SHALL CONNECT 2" DRAIN TO LAVATORY VERTICAL DRAIN AS PER PLAN SHALL PROVIDE TEST & CERTIFICATIONS FOR ALL BACKFLOW PREVENTERS RE TEST THE SYSTEM SHALL PERM CAP WATER CLOSET VENT @ SAN TEE. |