Permit: T05PL01363

Parcel: 14023068A


Addresses:

5818 S PARK AV


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T05PL01363

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/13/2005 PLUMBING - FINAL Approved IVRS - Inspection :*
1) 25 PSI TEST FROM METER UNDERGROUND TO BLDG TO WATER HEATER, FURNACE AND STOVE OK
2) CORRECTION MADE
3) GAS CARD AT METER
10/07/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/06/2005 PLUMBING - FINAL Denied 1) BLDG EMPTY AND NO ACCESS
2) NO TEST
09/08/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) SECTION 303 INTERNATIONAL MECHANICAL CODE
09/06/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLEASE SEE NOTES FROM 9/2/05 INSPECTION. NO CHANGE FROM THAT DATED INSPECTION, SPOKE TO OWNERS REPRESENTATIVE AND ASKED THEM TO READ NOTES AND COMPLY, THEN CALL FOR INSPECTION
09/02/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GAS PIPE TO BE 18" BELOW GRADE WHERE IT CROSSES DRIVEWAYS
2) PIPE TO BE IN TRENCH
3) TAPE AND PRIMER REQUIRED 6" TO EACH SIDE OF JOINTS AND TOOL MARKS
4) PRESSURE TEST REQUIRED ON ENTIRE SYSTEM
5) WATER HEATER WILL REQUIRE WEATHER PROOF ENCLOSURE WITH APPROVED GAS SHUT OFF VALVE
6) ALL APPLIANCES REQUIRE AGA OR CSA APPROVED GAS SHUT OFF VALVES
7) FURNACE WILL REQUIRE RIDGID PIPE NIPPLE THRU APPLIANCE HOUSING. CORRECT VENT PIPING AND TERMINATION OF VENT WITH APPROVED VENT CAP
8) CAP OFF ALL SANITARY SEWER PIPING THAT IS OPEN CREATING AN UN-SANITARY CONDITION
9) YOUR FURNACE IS INSTALLED IN VIOLATION OF SECTION 303.3 F 2000 INTERNATIONAL MECHANICAL CODE. THIS WILL REQUIRE PERMITTING AND CORRECTION
08/31/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) GAS PIPE TO BE 18" BELOW GRADE WHERE IT CROSSES DRIVEWAYS
2) PIPE TO BE IN TRENCH
3) TAPE AND PRIMER REQUIRED 6" TO EACH SIDE OF JOINTS
4) PRESSURE TEST REQUIRED ON ENTIRE SYSTEM