Permit: T05PL01350

Parcel: 112062880


Addresses:

2007 E GRANT RD #01


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T05PL01350

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/02/2005 PLUMBING - FINAL Approved IVRS - Inspection :*
1) CORRECTION MADE
2) GAS CARD AT METER
08/26/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) VENT PIPING SHALL RISE AT 2 PERCENT MINIMUM PER NOTE #3 AND DBL WALL REQUIRES 1" MINIMUM CLEARANCE FROM COMBUSTIBLES, SINGLE WALL REQUIRES 6" MINIMUM CLEARANCE FROM COMBUSTIBLES AND BE SUPPORTED PROPERLY
08/25/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) SEE NOTE #4 AND PROVIDE 1" MINIMUM CLEARANCE FROM COMBUSTIBLES ON DBL WALL VENT PIPING
08/23/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE UPPER COMBUSTION AIR
2) MAKE CORRECT CONNECTION FROM SINGLE WALL WYE FITTING TO DBL WALL PIPING
3) HORIZONTAL VENT PIPING TO RISE AT 2 PERCENT MINIMUM
4) PROVIDE PETITION OF APPEAL ON SITE FOR ALT. FORM OF T & P RELIEF WITH NIPPLE OUT OF 125 POUND PRESSURE RELIEF
08/22/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*