Permit: T05PL01344

Parcel: 131030530


Addresses:

5102 E 24TH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/25/2005 PLUMBING - FINAL Approved IVRS - Inspection :*
1) CORRECTION MADE
2) 12 PSI TEST TO WATER HEATER AND FURNACE FROM METER NEW 3/4" P.E. TO EXISTING SERVICE ENTRY OK
3) GAS CARD AT METER
08/23/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PLASTIC GAS PIPING REQUIRES 18" MINIMUM DEPTH FOR COVER ON PIPING
2) WATER HEATER APPLIANCE GAS SHUT OFF VALVE TO BE IN ACCESSIBLE LOCATION
3) PROVIDE BONDING OF BLDG GAS PIPING
4) VENT FROM WATER HEATER TO BE SINGEL WALL TO WYE CONNECTION WITH 3-GALV SCREWS AT ALL JOINTS OF VENT PIPING FROM BOTH FURNACE AND WATER HEATER