Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T05PL01339
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/21/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
09/15/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NO ADDRESS POSTED-I HAVE POLITELY ASKED SEVERAL TIMES TO HAVE YOUR ADDRESS POSTED. WHY WON'T YOU COMPLY? 2) BOTH PERMITS MUST BE ON SITE AT TIME OF INSPECTION |
|
09/13/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PLANS AND PERMITS TO BE ON SITE |
|
08/24/2005 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) GAS SYSTEM OK SEE NOTE #3, SPOKE TO OWNERS WHEN PERMIT IS OBTAINED THIS PERMIT WILL RELEASE GAS CARD |
|
08/22/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NO ADDRESS POSTED 2) GATE LOCKED 3) NO MESSAGE LEFT OR CONTACT NUMBER |
|
08/22/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 03050 - 11 PSI TEST FROM METER LOCATION NEW PIPING ABOVE GRADE TO STOVE, WATER HEATER, AND FURNACE ONLY (pARTIAL APPROVAL) 2) 03090 - VENT FROM WATER HEATER TO RUN IN UPWARD DIRECTION TO POINT OF TERMINATION AND HAVE 1" MINIMUM CLEARANCE FROM COMBUSTABLES 3) WASTE AND VENT SYSTEM IN BASEMENT IS A REPIPE THAT REQUIRES PERMIT FROM CITY WITH CORRECT SUPPORT, DRAINAGE FITTINGS, VENTING, COUPLINGS OF FITTINGS AND PIPE. |