Permit: T05PL01339

Parcel: 117060710


Addresses:

423 E 9TH ST


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T05PL01339

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/21/2005 PLUMBING - FINAL Approved IVRS - Inspection :*
09/15/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) NO ADDRESS POSTED-I HAVE POLITELY ASKED SEVERAL TIMES TO HAVE YOUR ADDRESS POSTED. WHY WON'T YOU COMPLY?
2) BOTH PERMITS MUST BE ON SITE AT TIME OF INSPECTION
09/13/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PLANS AND PERMITS TO BE ON SITE
08/24/2005 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1) GAS SYSTEM OK SEE NOTE #3, SPOKE TO OWNERS WHEN PERMIT IS OBTAINED THIS PERMIT WILL RELEASE GAS CARD
08/22/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) NO ADDRESS POSTED
2) GATE LOCKED
3) NO MESSAGE LEFT OR CONTACT NUMBER
08/22/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 03050 - 11 PSI TEST FROM METER LOCATION NEW PIPING ABOVE GRADE TO STOVE, WATER HEATER, AND FURNACE ONLY (pARTIAL APPROVAL)
2) 03090 - VENT FROM WATER HEATER TO RUN IN UPWARD DIRECTION TO POINT OF TERMINATION AND HAVE 1" MINIMUM CLEARANCE FROM COMBUSTABLES
3) WASTE AND VENT SYSTEM IN BASEMENT IS A REPIPE THAT REQUIRES PERMIT FROM CITY WITH CORRECT SUPPORT, DRAINAGE FITTINGS, VENTING, COUPLINGS OF FITTINGS AND PIPE.