Permit: T05PL01311

Parcel: 133030430

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/04/2005 PLUMBING - FINAL Approved IVRS - Inspection :*
09/14/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PETITION OF APPEAL #2005.244
2) CORRECT VENTING FROM FURNACE
09/07/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) WATER HEATER TEMPERATURE AND PRESSURE RELIEF DRAIN PIPING TO BE RIDGID PIPE GRAVITY DRAIN TO DAYLIGHT OR PROVIDE PETITION OF APPEAL SIGNED BY CITY ON SITE WITH CORRECT INSTALLATION
2) VENT FROM FURNACE TO HAVE 6" MINIMUM CLEARANCE FROM COMBUSTIBLES WHEN SINGLE WALL
3) PROVIDE CORRECT VENT CONNECTION FROM DRAFT HOOD OF WATER HEATER TO VENT PIPE
4) VENTS FROM FURNACE TO BE 2' ABOVE, WATER HEATER VENT TO BE 3' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF COOLER INTAKE
5) PROVIDE AGA OR CSA APPROVED SHUT OFF VALVES FOR ALL APPLIANCES