Permit: T05PL01289

Parcel: 134043140


Addresses:

602 S STAUNTON DR

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/10/2005 PLUMBING - FINAL Approved IVRS - Inspection :*
1) PETITION OF APPEAL #2005.225 ON SITE
2) NEW 1 1/2 FROM METER TO OVERHEAD TO WATER HEATER, DRYER, GAS, FIREPLACE (LOG LIGHTER) AND ROOF TOP UNIT 15 PSI TEST OK
3) GAS CARD AT METER
08/09/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TEST SHALL HOLD MINIMUM 10 PSI FOR 15 MINUTES WITH NO PRESSURE DROP
2) REINSTALL ELECTRICAL GROUNDING CLAMP
3) PROVIDE BONDING OF BLDG GAS PIPING
4) PETITION OF APPEAL FOR ALTERNATE FORM OF TEMPERATURE AND PRESSURE RELIEF TO BE ON SITE SIGNED BY CITY FOR WATER HEATER