Permit: T05PL01285

Parcel: 107080280


Addresses:

802 W VANOVER RD

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
10/11/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
08/24/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GAS SYSTEM SHALL HAVE 10 PSI MINIMUM TEST PRESSURE ON ENTIRE SYSTEM AT TIME OF INSPECTION
2) GAS PIPING SHALL NOT BE INSTALLED UNDERGROUND UNDER PORCH OR STRUCTURE
3) WATER HEATER TEMPERATURE AND PRESSURE RELIEF DRAIN PIPING SHALL TERMINATE 6" TO 24" ABOVE FINISH GRADE
4) PROVIDE STAPLE BASE FOR WATER HEATER
5) PROVIDE 3-GALV SCREWS AT EACH JOINT OF WATER HEATER AND FURNACE VENT PIPING
6) EXPOSE ALL GAS PIPING IN DITCH PROVIDE MINIMUM 12" BURIAL DEPTH
7) VENT FROM FURNACE WHEN WITHIN 10' OF COOLER INTAKE TO BE 2' ABOVE TOP OF COOLER INTAKE WITH APPROVED VENT MATERIAL AND VENT CAP
08/22/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) I GOT YOUR MESSAGE, HOWEVER, YOU NEGLECTED TO LEAVE YOUR PHONE NUMBER
08/18/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) UNABLE TO INSPECT-DOGS IN YARD