Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/11/2005 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 08/24/2005 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GAS SYSTEM SHALL HAVE 10 PSI MINIMUM TEST PRESSURE ON ENTIRE SYSTEM AT TIME OF INSPECTION 2) GAS PIPING SHALL NOT BE INSTALLED UNDERGROUND UNDER PORCH OR STRUCTURE 3) WATER HEATER TEMPERATURE AND PRESSURE RELIEF DRAIN PIPING SHALL TERMINATE 6" TO 24" ABOVE FINISH GRADE 4) PROVIDE STAPLE BASE FOR WATER HEATER 5) PROVIDE 3-GALV SCREWS AT EACH JOINT OF WATER HEATER AND FURNACE VENT PIPING 6) EXPOSE ALL GAS PIPING IN DITCH PROVIDE MINIMUM 12" BURIAL DEPTH 7) VENT FROM FURNACE WHEN WITHIN 10' OF COOLER INTAKE TO BE 2' ABOVE TOP OF COOLER INTAKE WITH APPROVED VENT MATERIAL AND VENT CAP |
|
| 08/22/2005 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1) I GOT YOUR MESSAGE, HOWEVER, YOU NEGLECTED TO LEAVE YOUR PHONE NUMBER |
|
| 08/18/2005 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1) UNABLE TO INSPECT-DOGS IN YARD |