Permit: T05PL01258

Parcel: 130080030


Addresses:

3775 E 27TH ST


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T05PL01258

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
08/31/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
12 PSI TEST IS OK
LEFT GAS CARD
ALL CORRECTIONS HAVE BEEN MADE
OK TO BACKFILL TRENCH
08/18/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SEE NOTE #1 AND #4
08/05/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 10 PSI TEST SHALL BE IN PLACE AT TIME OF INSPECTION AND HOLD FOR 15 MINUTES WITH NO PRESSURE LOSS
2) PROVIDE PIPE PRIMER THEN TAPE ALL JOINTS AND FITTING AND TOOL MARKS ON UNDERGROUND PIPING. PRIMER IS A TYPE OF GLUE NUT PAINT
3) PROVIDE FIRM BONDING UNDER ALL IN GROUND PIPING
4) VENT FROM WATER HEATER SHALL BE APPROVED MATERIAL FROM DRAFT HOOD TO DBL WALL AT CEILING PENETRATION
5) WATER HEATER TEMPERATURE AND PRESSURE RELIEF DRAIN PIPING TO BE FULL SIZE RIDGID APPROVED PIPING AND GRAVITY DRAIN TO DAY LIGHT
6) VENTS FROM WATE HEATER TO BE 3' ABOVE, FURNACE 2' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF COOLER INTAKE WITH APPROVED DBL WALL VENT PIPING AND VENT CAP