Permit: T05PL01255

Parcel: 117082690


Addresses:

910 S 3RD AV #03

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
08/26/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
08/11/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THIS IS NOT A RECONNECT, NEW PIPING HAS BEEN ADDED TO ROOF TOP UNITS
2) 1 NO GAS PIPING SHALL RUN IN OR UNDERGROUND BENEATH ANY BLDG OK STRUCTURE
08/04/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE WORKING PRESSURE GAUGE ON UNIT #4 WITH MINIMUM 10 PSI TEST TO HOLD FOR 15 MINUTES.
2. PROVIDE ACCESS TO UNIT #3 FOR GAS INSPECTION.
3. PROVIDE PERMITS FROM CITY FOR NEW AC UNITS.
4. ALL APPLIANCES REQUIRE AGA OR CSA GAS SHUTOFF VALVES.
THIS IS NOT A COMPLETE LIST.