Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/12/2005 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 08/10/2005 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 14 PSI TEST IS OK 2) BOND THE NEW GAS LINE WITH THE ELECTRIC SERVICE 3) PROVIDE ACCESS TO ALL APPLIANCES INSIDE THE HOUSE 4) AN ADULT MUST BE PRESENT |
|
| 08/03/2005 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 100 PRESSURE GAUGE NOT ACCEPTABLE-USE A 15 POUND GAUGE 2) NEED ACCESS TO ALL GAS APPLIANCES INSIDE HOUSE 3) ALL APPLIANCES MUST BE BROUGHT UP TO CODE 4) BE SURE TO USE APPROVED GAS SHUT OFF VALVES, T & P DRAIN LINE ON WATER HEATER 5) DBL WALL VENT PIPE ON WATER HEATER, EXTEND FURNACE VENT 2' ABOVE EVAP COOLER 6) FURNACE VENT MUST ALSO BE DBL WALL PIPE |