Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2005 | PLUMBING - SEWER HCS CONNECT | Approved | IVRS - Inspection :* 1) WATER TEST FROM BLDG THRU 2-WAY CLEANOUT TO HCS IN STREET OK. CORRECTION MADE |
|
| 08/01/2005 | PLUMBING - SEWER HCS CONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE DUCTILE IRON 5' BOTH SIDES OF H20 MAIN WHEN SEWER DOES NOT HAVE MINIMUM 2' SEPERATION 2) PROVIDE TEST ON ENTIRE SEWER PIPING 3) PROVIDE FIRM BONDING FOR ALL PIPING 4) HAVE RIGHT OF WAY PERMIT ON SITE |