Permit: T05PL01212


Addresses:

9201 E BROADWAY BL

Inspection Status: Not ready for Inspection

Inspection History: SITE - SEWER

Date Description Inspector Results Comments
02/15/2007 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
1. SHALL PROVIDE AUTHORIZATON TO DISCHARGE PER PCDEQ AS REQUESTED IF PCDEQ INVOLVEMENT.
2. SHALL HAVE TRACER WIRE TO SURFACE
3. MANHOLES COVERS & END OF LINE CLEANOUTS TO BE CONCRETED IN PLACE.
05/09/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
MANHOLE #2 VACUUM TEST OK
MANHOLE #3 VACUUM TEST OK
MANHOLE #2 HOLEDAISE TEST OK
04/21/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
MANHOLE BASES POURED - OK TO STACK
04/20/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
ALL PIPING AIR TEST OK
AIR PRESSURE TEST 6" FROM MANHOLE #2 INCLUDING HCS LATERALS UPSTREAM TO END OF LINE CLEANOUT #1 OK
AIR PRESSURE TEST 8" FROM MANHOLE #2 TO MANHOLE #3 INCLUDING HCS LATERALS OK
AIR PRESSURE TEST FROM MANHOLE #2 TO MANHOLE #1 INCLUDING HCS LATERAL OK
AIR PRESSURE TEST FROM MANHOLE #3 TO END OF LINE CLEANOUT #2 INCLUDING HCS LATERALS OK
04/19/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
FROM MANHOLE #2 TO CLEANOUT #2 INCLUDING (2) 6" HCS LATERALS TO BLD 5 + BLD 6
SHADING, BEDDING, LAYING, TRACER OK
PENDING NOTES FROM 4/12/06
04/18/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
8" SDR 35 FROM MANHOLE #2 TO MANHOLE #3 INCLUDING (2) 6" HCS LATERALS TO BLD. #1 & BLD. #2
6" HCS LATERAL TO BLD 8 FROM 6" UPSTREAM OF
MANHOLE #2.
6" UPSTREAM OF MANHOLE #2 TRANSITION TO DUCTILE BACK TO SDR 35 FOR END OF LINE CLEANOUT & 6" HCS LATERAL TO BLD. #4
BEDDING, SHADING, LAYING, TRACER OK
04/17/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
FROM STA 2 + 50 SDR35 6" TO TRANSITION TO 6" DIP INCLUDING 6" HCS LATERAL TO BLD 5
BEDDING, SHADING, LAYING, TRACER OK
04/13/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
8" SDR CONTINUES THRU INCLUDING 6" HCS LATERAL TO BLD 3 TO MANHOLE #2.
6" FROM MANHOLE #2 TO STATION 2 + 50 BEDDING, SHADING, LAYING TRACER OK
04/12/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
8" SDR FROM PUBLIC MANHOLE #1 100' NORTH TO STATION 0+00 TO 1+100 BEDDING, LAYING OK
1. WILL REQUIRE INDEPENDENT INSPECTION FOR ADEQ CERTIFICATION INCLUDING VERIFICATION OF GRADE, PRESSURE TESTING OF PIPING, VACUUM TESTING OF MANHOLES WITH ADEQ AUTHORIZATION TO DISCHARGE AT LATER DATE.