Inspection History Details
Permit: T05PL01212
Inspection Status: Not ready for Inspection
Inspection History: SITE - SEWER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/15/2007 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* 1. SHALL PROVIDE AUTHORIZATON TO DISCHARGE PER PCDEQ AS REQUESTED IF PCDEQ INVOLVEMENT. 2. SHALL HAVE TRACER WIRE TO SURFACE 3. MANHOLES COVERS & END OF LINE CLEANOUTS TO BE CONCRETED IN PLACE. |
|
| 05/09/2006 | SITE - SEWER | Partial Approval | IVRS - Inspection :* MANHOLE #2 VACUUM TEST OK MANHOLE #3 VACUUM TEST OK MANHOLE #2 HOLEDAISE TEST OK |
|
| 04/21/2006 | SITE - SEWER | Partial Approval | IVRS - Inspection :* MANHOLE BASES POURED - OK TO STACK |
|
| 04/20/2006 | SITE - SEWER | Partial Approval | IVRS - Inspection :* ALL PIPING AIR TEST OK AIR PRESSURE TEST 6" FROM MANHOLE #2 INCLUDING HCS LATERALS UPSTREAM TO END OF LINE CLEANOUT #1 OK AIR PRESSURE TEST 8" FROM MANHOLE #2 TO MANHOLE #3 INCLUDING HCS LATERALS OK AIR PRESSURE TEST FROM MANHOLE #2 TO MANHOLE #1 INCLUDING HCS LATERAL OK AIR PRESSURE TEST FROM MANHOLE #3 TO END OF LINE CLEANOUT #2 INCLUDING HCS LATERALS OK |
|
| 04/19/2006 | SITE - SEWER | Partial Approval | IVRS - Inspection :* FROM MANHOLE #2 TO CLEANOUT #2 INCLUDING (2) 6" HCS LATERALS TO BLD 5 + BLD 6 SHADING, BEDDING, LAYING, TRACER OK PENDING NOTES FROM 4/12/06 |
|
| 04/18/2006 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 8" SDR 35 FROM MANHOLE #2 TO MANHOLE #3 INCLUDING (2) 6" HCS LATERALS TO BLD. #1 & BLD. #2 6" HCS LATERAL TO BLD 8 FROM 6" UPSTREAM OF MANHOLE #2. 6" UPSTREAM OF MANHOLE #2 TRANSITION TO DUCTILE BACK TO SDR 35 FOR END OF LINE CLEANOUT & 6" HCS LATERAL TO BLD. #4 BEDDING, SHADING, LAYING, TRACER OK |
|
| 04/17/2006 | SITE - SEWER | Partial Approval | IVRS - Inspection :* FROM STA 2 + 50 SDR35 6" TO TRANSITION TO 6" DIP INCLUDING 6" HCS LATERAL TO BLD 5 BEDDING, SHADING, LAYING, TRACER OK |
|
| 04/13/2006 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 8" SDR CONTINUES THRU INCLUDING 6" HCS LATERAL TO BLD 3 TO MANHOLE #2. 6" FROM MANHOLE #2 TO STATION 2 + 50 BEDDING, SHADING, LAYING TRACER OK |
|
| 04/12/2006 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 8" SDR FROM PUBLIC MANHOLE #1 100' NORTH TO STATION 0+00 TO 1+100 BEDDING, LAYING OK 1. WILL REQUIRE INDEPENDENT INSPECTION FOR ADEQ CERTIFICATION INCLUDING VERIFICATION OF GRADE, PRESSURE TESTING OF PIPING, VACUUM TESTING OF MANHOLES WITH ADEQ AUTHORIZATION TO DISCHARGE AT LATER DATE. |