Permit: T05PL01212


Addresses:

9201 E BROADWAY BL

Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - YARD WTR LINE/TEST

Date Description Inspector Results Comments
02/15/2007 PLUMBING - YARD WTR LINE/TEST Not ready for Inspection IVRS - Inspection :*
1. PROVIDE YELLOW PERMIT CARD
2. HAVE BACKFLOW DETAIL PLAN BULMARO PARRA-BUBADILLA DATED 11/20/06 APPROVED BY CITY PLAN CHECK (ROBERT SHERRY) FOR SITE WATER 909-909 RPDA INSTALLED.
08/08/2006 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
PIPING INSTALLED PER UNAPPROVED DRAWING
NEW 6" RP W/BELOW GRADE 6X8 INCREASER TIED INTO C-900 PIPING. CONNECTIONS OK. BACTERIA REPORT RECEIVED.
HAVE DRAWING APPROVED RECALL FOR FINAL INSPECTION.
05/24/2006 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
200 PSI TEST AT 8:30, 180 AT 10:30 NO LEAKAGE VISIBLE
PROVIDE REVISED APPROVED PLAN OF EXISTING WATER METER AREA WITH DETAIL OF THIS AREA OR INSTALL PER APPROVED PLAN.
05/22/2006 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
(8) 1 1/2 SERVICES FOR WATER FROM MAIN TO CORP STOP
05/19/2006 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
SOUTHEAST CORNER MADE UP TO 20' PAST 90 DEGREES FOR TEST
SOUTHWEST CORNER TO DRAIN ASSEMBLY OK
WILL NEED TO SEE SERVICES
WILL NEED TO SEE TESTING, CHLORINIZATION & BACTERIA REPORT.
05/18/2006 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
FROM STA 10+65.57 NORTH AROUND LOOP PER TO 10' NORTH OF STA 15+47.18 OK
BEDDING, LAYING, TRACER, SHADING, RESTRAINT.
1. NEED TO SEE SOUTHWEST & SOUTHEAST CORNER COMPLETED TO DRAIN ASS. & RPBA ASSEMBLY.
05/17/2006 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
STARTED INSTALL OF 8" C-900 AT STATION 10+65.5 INSTALLING 8" AND 6" WITH TRACER WIRE.
BEDDING IS OK
CONTRACTOR INSTALL PER TUCSON WATER STANDARDS.
PLAN SHOWS TAP OF EXISTING MAIN FOR SUPPLY THERE IS AN EXISTING 6" SUPPLY ON SITE, HAVE PLAN REVISED OR INSTALL PER PLAN WITH CORRECT BACKFLOW PROTECTION FOR THIS PROJECT.