Inspection History Details
Permit: T05PL01212
Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/15/2007 | PLUMBING - YARD WTR LINE/TEST | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE YELLOW PERMIT CARD 2. HAVE BACKFLOW DETAIL PLAN BULMARO PARRA-BUBADILLA DATED 11/20/06 APPROVED BY CITY PLAN CHECK (ROBERT SHERRY) FOR SITE WATER 909-909 RPDA INSTALLED. |
|
| 08/08/2006 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* PIPING INSTALLED PER UNAPPROVED DRAWING NEW 6" RP W/BELOW GRADE 6X8 INCREASER TIED INTO C-900 PIPING. CONNECTIONS OK. BACTERIA REPORT RECEIVED. HAVE DRAWING APPROVED RECALL FOR FINAL INSPECTION. |
|
| 05/24/2006 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 200 PSI TEST AT 8:30, 180 AT 10:30 NO LEAKAGE VISIBLE PROVIDE REVISED APPROVED PLAN OF EXISTING WATER METER AREA WITH DETAIL OF THIS AREA OR INSTALL PER APPROVED PLAN. |
|
| 05/22/2006 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* (8) 1 1/2 SERVICES FOR WATER FROM MAIN TO CORP STOP |
|
| 05/19/2006 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* SOUTHEAST CORNER MADE UP TO 20' PAST 90 DEGREES FOR TEST SOUTHWEST CORNER TO DRAIN ASSEMBLY OK WILL NEED TO SEE SERVICES WILL NEED TO SEE TESTING, CHLORINIZATION & BACTERIA REPORT. |
|
| 05/18/2006 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* FROM STA 10+65.57 NORTH AROUND LOOP PER TO 10' NORTH OF STA 15+47.18 OK BEDDING, LAYING, TRACER, SHADING, RESTRAINT. 1. NEED TO SEE SOUTHWEST & SOUTHEAST CORNER COMPLETED TO DRAIN ASS. & RPBA ASSEMBLY. |
|
| 05/17/2006 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* STARTED INSTALL OF 8" C-900 AT STATION 10+65.5 INSTALLING 8" AND 6" WITH TRACER WIRE. BEDDING IS OK CONTRACTOR INSTALL PER TUCSON WATER STANDARDS. PLAN SHOWS TAP OF EXISTING MAIN FOR SUPPLY THERE IS AN EXISTING 6" SUPPLY ON SITE, HAVE PLAN REVISED OR INSTALL PER PLAN WITH CORRECT BACKFLOW PROTECTION FOR THIS PROJECT. |