Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/04/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 13 PSI AIR TEST NOW 6" SCOTCH COAT FROM MOTOR UNDERGROUND TO BUILDING UP TO WATER HEATER OVERHEAD TO ROOF TOP UNIT AND STOVE OK CORRECTION MADE -- GAS CARD AT MOTOR |
|
| 08/03/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WHERE UNIONS ARE NECESSARY LEFT-RIGHT NIPPLES AND COUPLINGS SHALL BE USED 2) GAS PIPING PENETRATION THRU ROOK REQUIRE APPROVED FLASHING 3) YOUR GAS PIPE SIZING DOE NOT MEET MINIMUM REQUIREMENTS FOR BTU DEMAND AT FURTHEST FIXTURE. PLEASE SEE 94 UPC TABLE 12-3 |