Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/26/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) ALL CORRECTIONS HAVE BEEN MADE |
|
07/21/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHALL PROVIDE PROPER TEST GAUGE FOR LOW PRESSURE GAS 2) SHALL PROVIDE A DBL WALL FLU CAP FOR WATER HEATER 3) SHALL REPLACE T & P VALVE THAT IS STUCK SHUT 4) SHALL REMOVE COMBUSTIBLE MATERIAL FROM AROUND WATER HTR 5) SHALL EXTEND FURNACE FLU VENT 2' ABOVE COOLER 6) SHALL HARD PIPE OUT OF FURNACE HOUSING THEN CONNECT THE FLEX CONNECTOR 7) SHALL REMOVE THE UNION AT BLDG SERVICE OR REPLACE WITH RIGHT AND LEFT HAND NIPPLE OR LOCATE A GAS SHUT OFF BEFORE THE UNION 8) RE-TEST THE SYSTEM 10 POUND MINIMUM |