Permit: T05PL01116


Addresses:

825 W CONGRESS ST


Inspection Status: Approved

Inspection History: SITE - SEWER

Permit Number - T05PL01116

Inspection Description - SITE - SEWER

Inspection Status - Approved

Date Description Inspector Results Comments
09/19/2007 SITE - SEWER Approved IVRS - Inspection :*
08/21/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
FROM MANHOLE #17 TO MANHOLE #18 AIR TEST 6" SDR35 INCLUDING HCS'S OK 2/10 LOSS
08/18/2006 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
08/17/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
- PUBLIC MANHOLE #3 TO #4 AIRTEST OK NO LOSS
- MANHOLE #3 PUBLIC - VACUUM TEST OK 1" LOSS AT 24 SECONDS.
- MANHOLE #4 PUBLIC TO #5 PUBLIC AIR TEST OK 2/10 LOSS
- MANHOLE #4 PUBLIC TO #9 PUBLIC AIR TEST OK NO LOSS
- PRIVATE MANHOLE #3 VACUUM TEST OK 1/2" LOSS AT 16 SECONDS.
- PRIVATE MANHOLE #2 VACUUM TEST OK 1/2" LOSS AT 16 SECONDS.
- PRIVATE MANHOLE #2 TO #3 AIR TEST OK NO LOSS
- PRIVATE MANHOLE #1 VACUUM TEST OK 1/2" LOSS
- PRIVATE MANHOLE #5 TO #6 AIRTEST OK 4/10 LOSS
- PRIVATE MANHOLE #14 TO #15 AIRTEST OK NO LOSS
- PRIVATE MANHOLE #15 TO #16 AIRTEST OK 1/10 LOSS.
08/16/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
BETWEEN MANHOLE #7 & #8 LOT #79 HCS TAP & LATERAL REPAIR OK
08/15/2006 SITE - SEWER Partial Approval FROM MANHOLE #16 TO #15 LOTS #32, 33, 34 HCS TAPS & LATERAL REPAIR OK
FROM MANHOLE #3 TO #4 LOT #87 HCS TAPE & LATERAL REPAIR OK
BETWEEN MANHOLE #5 & 6 LOT #9 TAP & LATERAL REPAIR OK
LOT #85 TAP & LATERAL REPAIR OK
FROM MANHOLE #2 TO #3 LOT #98 HCS TAP & LATERAL REPAIR OK
LOT #96 HCS TAP & LATERAL REPAIR OK
FROM MANHOLE #1 & #2 LOT #95 HCS TAP & LATERAL REPAIR OK
08/15/2006 SITE - SEWER Partial Approval - 4.5 PSI TEST FROM MANHOLE #2 TO #3 OK NO LOSS
- 4.2 PSI TEST FROM MANHOLE #1 TO #2 OK 1/10 LOSS
- LOT #83 HCS TAP & LATERAL REPAIR BETWEEN MANHOLE
#7 & #8 OK
- 4.2 PSI TEST FROM MANHOLE #3 TO #4 FOR LOT #87
- 4.2 PSI TEST FROM MANHOLE #5 TO #6 SHALL RETEST
- 4.6 PSI TEST FROM MANHOLE #4 TO #5 OK NO LOSS
- LOT #35 & 36 HCS TAP & LATERAL REPAIR OK
- 5.0 PSI TEST FROM MANHOLE #4 TO #7 OK NO LOSS
08/14/2006 SITE - SEWER Partial Approval AIR TEST MH 6-7 .2 PSI LOSS OK
AIR TEST MH 11-12, .1 PSI LOSS OK
AIR TEST MH 12-13, .4 PSI LOSS OK
AIR TEST MH 7-8, .4 PSI LOSS OK

LOT 38 REPAIRED OK
LOT 85 REPAIRED OK
LOT 37 REPAIRED OK
08/11/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
LOT 56 INSPECTED OK
LOTS 57, 61 AND 90 HAVE BEEN REPAIRED OK
08/09/2006 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELLED
08/08/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
- LOT #21 HCS TAP OK BETWEEN MANHOLE #17 & 18
- LOT #46, 53, 54 HCS TAPS & LATERAL CORRECTED BETWEEN MANHOLE #11 & 12
- LOT #92 HCS TAP & LATERAL CORRECTED BETWEEN MANHOLE #6 & 5
- LOT #93 HCS COMES FROM MANHOLE #6
- LOT #44 HCS TAPE & LATERAL CORRECTED BETWEEN MANHOLE #12 & 13
08/07/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
4 PSI TEST MANHOLE #10 TO #11 NO PRESSURE LOSS OK
INCLUDING HCS LATERALS FOR LOT 47, 48, 49
VISUAL INSPECTION LOT #29
HCS TAP & LATERAL OK
LOT #52 HCS TAP & LATERAL REPAIR OK
BETWEEN MANHOLE #11 & 12
08/04/2006 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELLED
08/03/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
LOT #48 BETWEEN MANHOLE #10 TO MANHOLE #11 HCS TAP & LATERAL VISUAL.

MANHOLE #18 TO MANHOLE #17 LOT #30 HSC TAP CORRECTED, LOT #20 HCS TAP OK LOT #28 HCS TAP IS OK

NEED TESTING ONLY ON MANHOLE #10 TO #11 MANHOLE #11 TO #12 LOT #55 & LOT #45 HCS TAPS CORRECTED.
08/02/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
HCS TAP FOR LOT #47 FROM MANHOLE #10 TO #11 VISUAL OK
FROM MANHOLE #9 PRIVATE TO MANHOLE #9 PUBLIC INCLUDING HCS'S
TAPS & LATERALS ON 6" SDR 35 SEWER AIR TEST 4.4 AIR TEST NO DROP FOR 2"50
4.2 PSI FROM MANHOLE #6 TO #10 INCLUDING HCS LOT'S # 62, 63, 64
1/10 LOSS OK
07/28/2006 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELLED.
07/27/2006 SITE - SEWER Partial Approval IVRS - Inspection :*
- FROM MANHOLE #10 TO #11 HCS LATERAL & TAP FOR
LOT 49 OK
- FROM MANHOLE #10 TO #6 HCS LATERAL & TAP FOR LOT #62, #63, #64 OK
- SHALL EXPOSE HCS TAPS & LATERAL FOR ALL PRIVATE SEWER
- ALL CORRECTIONS SHALL REQUIRE RETESTING
- SHALL WITNESS VACUUM TESTING ON SELECTED PRIVATE MANHOLES TO VERIFY WLB RESULTS.
07/21/2006 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
LOT #49 HCS SADDLE TAP & LATERAL DOES NOT MEET DETAIL 3401 SADDLE IS INSTALLED BELOW CENTER OF FLOW LINE OF MAIN SEWER. LOT #48 IS INCORRECT. IT APPREARS THAT THERE IS A POSSIBILITY MORE HCS CONNECTIONS COULD BE INCORRECT.
07/20/2006 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
VIEWING OF TRANSITION OF DUCTILE IRON 8" TO 8" SDR 35 PAD ADAPTER OK
CONTRACTOR CALLED AS FAVOR BECAUSE OF UNSTABLE SOIL CONDITION AND RAIN. THIS IS UPSTREAM OF EXISTING MANHOLE #3
07/19/2006 SITE - SEWER Not ready for Inspection 1) FROM MANHOLE #6 TO 10P TRANSITION FROM SDR35 TO DUCTILE CORRECTION OK. SHALL TEST THIS SECTION OF PIPING
2) VIEWING OF HCS TAPS BETWEEN MANHOLD #9 AND 9P OK. SHALL TEST THIS SECTION. TOLD THIS EAS PROTECTED, TRIED TEST FAILED
07/13/2006 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
07/05/2006 SITE - SEWER Cancelled
07/05/2006 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELLED PER BELINDA
06/30/2006 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
VISUAL INSPECTION OF SDR35 BEDDING, SHADING & PIPE JOINT 1ST JOINT DOWN STREAM OF MANHOLE #18
PAGE 3 OF 18
1. PROVIDE APPROVED TRANSITION FROM DUCTILE TO SDR35 AT 1ST JOINT OF 6" UPSTREAM OF PUBLIC MANHOLE #6.
THIS TO BE RETESTED.
2. HCS LATERAL DESIGN SHALL MEET DETAIL #401 FROM PAGE #8 OF 18. ADDITIONAL HCS CONNECTIONS TO MAIN SEWER SHALL BE EXPOSED BY JERRY (GRANITE), WLB INSPECTOR TO BE ON SITE AT NEXT INSPECTION, AND POSSIBLE ADDITIONAL HCS CONNECTION SHALL BE EXPOSED.
06/13/2006 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
MET WITH JERRY GRANITE, WLB ENGINEERING SHALL REQUIRE EXPOSURE OF PIPING AT (5) LOCATIONS PAGE #5, #3, #8, #7, #9 DOCUMENTED ON FULL SIZE DRAWINGS ON SITE AND MINI DRAWING IN DSD. DUCTILE IRON PIPING MAY REQUIRE HOLIDAY'S TESTING AFTER VISUAL INSPECTION. AIR TESTING OF PIPING & VACUUM TESTING OF MANHOLES SHALL BE REQUIRED TO VERIFY INDEPENDENT ENGINEER'S RESULTS.
05/31/2006 SITE - SEWER Denied IVRS - Inspection :
See detailed listing on site.| 999*
SITE VISIT PER SUPERVISOR REQUEST, STATUS OF WORK AT SITE FOR SCHEDULED MEETING TODAY 5/31/06.
ENGINEERS ON SITE SURVEYING FOR BLUE TOP.
SITE STILL IN DIRT STATE WITH SEWER WORK (PRIVATE) COVERED WITHOUT CITY INSPECTION PER PAST INSPECTION HISTORY.
05/17/2006 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
1. SEE NOTES FROM 8/16/05
CONTRACTOR IS FULLY AWARE OF WHAT WAS REQUIRED BY COT AND CHOSE TO COVER W/O INSPECTION.
04/27/2006 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
09/15/2005 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
08/16/2005 SITE - SEWER Not ready for Inspection IVRS - Inspection :*
1) PRE CON MEETING WITH MIKE AND DAN
2) REVIEWED CHART
3) REVIEWED PDEQ REQUIREMENTS