Permit: T05PL01083

Parcel: 112030270


Addresses:

2533 E KLEINDALE RD

Inspection Status: Partial Approval

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
07/07/2005 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :* 15 PSI TEST IS OK. LEFT GAS CARD. CORRETIONS HAVE BEEN MADE. NO 12 WIRE NOT ADEQUATE FOR THE BOND JUMPER. USE MIN #6 . RECALL FOR INSPECTION.
07/06/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999* REMOVE UNION & UNESSESARY GAS PIPING IN FURNACE CLOSET. RETEST SYSTEM. PROVIDE AN APPROVED SHUT OFF VALVE @ STOVE. RECALL FOR INSPECTION. ALSO PROVIDE A BOND JUMPER FROM THE WATER LINE TO THE GAS LINE.
06/29/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :* 1) NOT READY FOR INSPECTION