Inspection History Details
Inspection Status: Partial Approval
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/07/2005 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* 15 PSI TEST IS OK. LEFT GAS CARD. CORRETIONS HAVE BEEN MADE. NO 12 WIRE NOT ADEQUATE FOR THE BOND JUMPER. USE MIN #6 . RECALL FOR INSPECTION. | |
| 07/06/2005 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* REMOVE UNION & UNESSESARY GAS PIPING IN FURNACE CLOSET. RETEST SYSTEM. PROVIDE AN APPROVED SHUT OFF VALVE @ STOVE. RECALL FOR INSPECTION. ALSO PROVIDE A BOND JUMPER FROM THE WATER LINE TO THE GAS LINE. |
|
| 06/29/2005 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY FOR INSPECTION |