Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/26/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) ALL CORRECTIONS HAVE BEEN MADE |
|
| 07/22/2005 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1) PROBLEM: YOU HAVE DBL WALL PIPE, B-1 DOWN THRU ROOF. YOU HAVE DBL WALL PIPE UP FROM WATER HTR. DRAFT BONNET IN THE CENTER IS ONE SINGLE WALL 45 DEGREE ELBOW 2) SUGGEST: REMOVE DBL WALL PIPE, BELOW 45 DEGREE ? COMPLETE W/SINGLE WALL DOWN TO TOP OF WATER HEATER |
|
| 07/20/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GAS PRESSURE TEST IS OK 2) GAS SHUT OFF VALVES OK 3) NOTE: SHALL PROVIDE EITHER SINGLE WALL OR DBL WALL WALL FLU VENT ALL THE WAY TO APPLIANCE COLLAR AND PROVIDE (3) SHEET METAL SCREWS PER JOINT 4) SHALL PROVIDE BONDING ON GAS LINE #3 WIRE MIN. 5) SHALL EXTEND FURNACE FLU VENT MIN OF 2' ABOVE COOLER AND WATER HTR FLU VENT 3' AVOVE COOLER 6) OK TO BACKFILL TRENCH |