Permit: T05PL01040

Parcel: 122170710

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/22/2005 PLUMBING - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
2) LEFT GAS CARD
06/21/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 20 PSI TEST IS OK. PROVIDE MIN. 1" CLEARANCE FROM WATER HEATER VENT TO COMBUSTIBLE. SECURE WATER HEATER VENT. PROVIDE MIN. 3 SCREWS IN CONNECTOR TO DRAFT DIVERTER & DOULBE WALL. PROVIDE A 3/4" DIAMETER DRAIN ON T & P VALVE DOWN TO 24" FROM GROUND. PROVIDE A BOND JUMPER TO GAS PIPE. NOT NECESSARY TO EXTEND WATER HEATER VENT SO HIGH IF ARTHER THAN 10' FROM COOLER.