Permit: T05PL01029

Parcel: 133410120


Addresses:

9530 E BAKER ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
06/24/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :* 12 PSI AIR TEST FROM NEW METER LOCATION TO WATER HEATER DRYER, AND ROOF TOP UNIT ONLY.
06/21/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :* 1) TEST TO HOLD MINIMUM 10 PSI FOR 15 MINUTES. 2) PIPING IN ATTIC SPACE TO BE SUPPORTED PROPERLY AND CHANGES OF DIRECTION REQUIRES FITTINGS. 3) THREAD PROTECTORS ARE NOT COUPLINGS USE APPROVED COUPLINGS OR WHERE UNIONS ARE NECESSARY LEFT & RIGHT NIPPLES & COUPLINGS SHALL BE USED. 4) PROVIDE BONDING OF BUILDING GAS PIPING.