Permit: T05PL01004

Parcel: 130030910


Addresses:

1508 S BRISTOL AV

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
06/23/2005 PLUMBING - FINAL Approved IVRS - Inspection :* APPROVED
06/15/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) VENT FROM WATER HEATER TO BE INSTALLED IN DIRECTION OF FLOW ARROW, PROVIDE 1" MINIMUM CLEARANCE FROM VENT MATERIAL AND PLYWOOD OF ROOF STRUCTURE, AND PROVIDE METAL APPROVED ROOF FLASHING FOR WATER HEATER VENT
2) PROVIDE BONDING OF BLDG GAS PIPING WITH 2 BONDING CLAMPS AND #4 COPPER WIRE FROM GAS PIPING TO BLDG COLD WATER PIPING. PLEASE CALL IN 03090 AFTER COMPLETION
06/14/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :* 1) PROVIDE ROOF FLASHINGS AT ALL PENETRATIONS THRU ROOF AT GAS PIPING. 2) THREAD PROTECTORS ARE NOT APPROVED COUPLINS, APPROVED COUPLNGS SHALL BE USED. 3) WHERE UN?? ARE NECESSARY LEFT-RIGHT NIPPLES & COUPLINGS SHALL BE USED.4) PROVIDE 10 X10" LOWER COMBUSTION AIR OPENING FOR WATER HEATER. 5) SECURE GAS PIPING DROP AT WATER HEATER. 6) SECURE ALL GAS PIPING ON ROOF. RETEST AND CALL IN.