Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T05PL00963
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) ALL CORRECTIONS HAVE BEEN MADE OK 2) OK FOR C OF O 3) UCC LEFT AT METER |
|
| 07/22/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 18 P.S.I TEST IS OK - WATER HEATER VENT NOT CONNECTED PROPERLY INSIDE CLOSET. PROVIDE MIN. 3 SCREWS IN ALL JOINTS OF VENT CONNECTORS DO NOT USE TAPE - SECURE THE DOUBLE WALL VENT PIPE ON THE ROOF & PROVIDE AN APPROVED ROOF JACK ON VENT PIPE - PROVIDE A MIN. 1" CLEARANCE FROM COMBUSTIBLE WHERE VENT PENETRATES THE ROOF -- SECURE DRAFT DIVERTER ON WATER HEATER. |
|
| 07/07/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ONCE AGAIN NO ONE HOME. PLEASE RESCHEDULE AN INSPECTION WHEN AN ADULT MAY BE PRESENT. 2) SHALL PAY A REISNPECTION FEE PRIOR TO THE NEXT INSPECTION. |
|
| 06/30/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*NO ONE HOME! |
|
| 06/22/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) PLEASE SCHEDULE AN INSPECTION WHEN SOMEONE WILL BE HOME |
|
| 06/08/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHALL PROVIDE DBL WALL FLU VENT ABOVE ROOF AND PROVIDE AN APPROVED B-1 CAP 2) FLU VENT THRU ROOF SHALL TERMINATE A MINIMUM OF 3'-0" ABOVE COOLER 3) SHALL PLUG WATER HTR DRAIN PAN |