Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/01/2005 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 05/26/2005 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 10 PSI TEST SHALL HOLD FOR 15 MINUTES WITH NO PRESSURE DROP 2) PROVIDE 10 X 10 OR 100 SQUARE INCHES UPPER AND LOWER COMBUSTION AIR OPENING FOR WATER HEATER 3) PROVIDE BONDING OF BLDG GAS PIPING 4) SECURE GAS PIPING IN FURNACE AREA 5) THREAD PROTECTORS ARE NOT APPROVED COUPLINGS (AT SERVICE ENTRY LOCATION) |