Permit: T05PL00911

Parcel: 131113400


Addresses:

5718 E 35TH ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
06/14/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :* NEW 1" SCOTCH COAT UNDERGROUND TO BUILDING UP TO EXISITING TO WATER HEATING STOVE & FURNACE OK. 10 PSI TEST OK. CORRECTIONS MADE. GAS CARD AT METER. 889-1888
06/01/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) SHALL REMOVE UNION BY METER AND LOCATE AN AGA OR CSA GAS SHUT OFF VALVE BEFORE THE UNION @ HOUSE SUPPLY. 2) SHALL REMOVE FLEX LINE IN T & P DRAIN AND RUN FULL SIZE 3/4" PIPE AND TERMINATE 6" A.F.F. 3) SHALL PROVIDE (3) SHEET METAL SCREWS PER JOINT @ WATER HEATER FLU VENT 4) SHALL HARD PIPE OUT OF FURNACE HOUSING THEN CONNECT FLEX CONNECTOR. 5) SHALL PROVIDE AGA OR CSA GAS SHUT OFF VALVES @ RANGE AND WATER HEATER. 6) SHALL EXTEND GAS SUPPLY TO WATER HTR. 7) RE TEST THE SYSTEM. 8) SHALL PROVIDE (2) 10 X10 LOUVER GRILLS FOR COMBUSTION RELIEF LOCATED 12" ABOVE FLOOR AND 12" BELOW CEILING. 9) SHALL PROVIDE # 6 GROUND WIRE TO GAS LINE FROM WATER BOND.