Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T05PL00846

Parcel: 126134610


Addresses:

4536 E DOUGLAS ST


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T05PL00846

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/31/2005 PLUMBING - FINAL Approved IVRS - Inspection :*
05/18/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :* 10 PSI TEST FROM METER NEW P.E UNDERGROUND TO EXISTING SERVICE ENTRY TO STOVE, WATER HEATER, AND FURNACE OK. 1) VENT FROM WATER HEATER TO BE 3" ABOVE TOP OF COOLER INTAKE WHEN WITHING 10' OF COOLER INTAKE WITH APPROVED VENT ???. MAKE CORRECTION CALL FOR REINSPECTION FOR GAS CARD.
05/16/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) YARD GAS PIPING IS COVERED WITHOUT INSPECTION,PLEASE EXPOSE ALL PIPING FROM METER TO CONNECTION TO BULDING SERVICE ENTRANCE FOR GAS PIPING, RETEST & CALL IN FOR INSPECTION.