Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T05PL00809
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/05/2005 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* 15 PSI AIR TEST FROM METER TO ROOF TOP UNITS, WATER HEATER, PIZZA OVEN, FRYER, STOVE TO/OVEN, GRILL TOP OK. CORRECTION MADE APPROVED. | |
05/04/2005 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* 1) VENT FROM WATER HEATER TO BE 3' ABOVE STRUCTURE WHERE WITHIN 10' FO BLDG OR STRUCTURE AND COOLER ? WITH APPROVED VENT CAP 2) SUPPORT GAS PIPING ON ROOF AT CORRECT INTERVALS 3) PROVIDE READABLE LISTING PLATES ON ALL APPLIANCES WITH GAS FLEXES THAT ARE RATED FOR BTU REQUIREMENT 4) WATER HEATER T & P DRAIN TO BE RIDGED FULL SIZE PIPING GRAVITY DRAIN TO DAYLIGHT 5) ANSUL VALVE REQUIRES SIGNAGE FOR IT'S LOCATION AND WHERE UNIONS ARE NECESSARY LEFT-RIGHT NIPPLES AND COUPLINGS SHALL BE USED |