Permit: T05PL00808

Parcel: 116170480


Addresses:

1125 W ERIE ST


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T05PL00808

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/10/2005 PLUMBING - FINAL Approved IVRS - Inspection :*1) GAS PRESSURE TEST IS OK. 2) GAS SHUT OFF VALVES OK. 3) WATER HEATER FLU VENT, OK. FURNACE FLU VENT OK. 4) NOTE: OWNER WILL REPLACE T & P VALVE
05/06/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE A MINIMUM 10 POUND PRESSURE TEST ON GAS PIPING
2) NEED TO HAVE ACCESS TO ALL GAS APPLIANCES
3) WATER HEATER VENT MUST HAVE A MINIMUM 1" CLEARANCE AT ROOF PENETRATIONS
4) EXTEND T & P RELIEF DRAIN TO WITHIN 24" OF THE FLOOR AND DO NOT HAVE THREADS ON BOTTOM OF PIPE