Permit: T05PL00780

Parcel: 12616005A


Addresses:

3921 E LA CRECIENTE

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
07/22/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
1) 15 PSI TEST FROM METER TO (2) WATER HEATER, (2) FURNACES, POOL HEATER AND OUTSIDE GAS GRILL ONLY OK
2) GAS CARD AT METER
3) OK TO COVER ALL UNDERGROUND PIPING
07/19/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
1) PLEASE HAVE SOMEONE PRESENT AT TIME OF REINSPECTION 1:55 PM
07/14/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :* 1) PLASTIC GAS PIPING REQUIRES 18" MINIMUM COVER IN UNDERGROUND. 2) ALL GAS PIPING THAT IS PLASTIC REQUIRES TRAILER WIRES. 3) PROVIDE COMBUSTION AIR UPPER LOWER FOR WATER HEATER ( EAST LOCATION) 4) VENT FROM WATER HEATER FURNACE TO BE MADE UP CORRECTLY AND BE SECURED PROPERLY. 5) PROVIDE BONDING OF BUILDING GAS PIPING . 6) GAS VALVE FOR GAS GRILL TO BE WITHIN 3' OF APPLIANCES. TERMINATE POOL HEATER GAS PIPING CORRECTLY. 7) PROVIDE TEST ON SINK DRAIN WITH APPROVED DRAINAGE FITTINGS
06/30/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
05/05/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/04/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THIS DOES NOT APPEAR TO BE A METER RELOCATE
2) PLEASE HAVE A GAS ISOMETRIC PLAN SHOWING ACTUAL GAS SYSTEM AND CITY APPROVED PLAN OF YOUR SCOPE OF WORK
3) ALL GAS SYSTEM TO HAVE 10 PSI MINIMUM PRESSURE TEST WITH NO DROP FOR 15 MINUTES
4) GAS PIPING CANNOT BE UNDERGROUND, UNDER BLDG OR STRUCTURE
5) WHERE UNIONS ARE NECESSARY LEFT AND RIGHT NIPPLES AND COUPLINGS SHALL BE USED
6) WILL NEED ACCESS TO ENTIRE GAS SYSTEM, IT WILL REQUIRE 94 UPC CODE REQUIREMENTS. PLEASE HAVE SOME ONE PRESENT TO PROVIDE ACCESS TO ENTIRE GAS SYSTEM AT TIME OF REINSPECTION. THIS IS NOT A COMPLETE LIST. NO ACCESS TO ENTIRE SYSTEM