Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2006 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection :* | |
| 02/23/2006 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ADDRESS MUST MATCH PERMIT WHERE IS TRACER WIRE? NO ADDRESS POSTED 2. PVC WATER PIPING TO BE INSTALLED WITH LETTERING UP FOR VERFICATION OF LISTING. 3. MAKE ALL CONNECTIONS, TEST ALL PIPE - REMOVE TEE WITH SCHRADER VALVE - ALL HOSE BIBS REQUIRE AVB WHICH IS NOT INSTALLED UNTIL RETAINING SCREW IS BROKEN OFF. NO TEST ON ABS REQUIRE 2% GRADE |
|
| 02/14/2006 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* - SOME PVC IS FOR DWV ONLY AND SOME OF THE PVC IS SUN DAMAGED. - PROVIDE PROPER MATERIAL, PROVIDE SUPPORT IN ALL AREAS. - PROVIDE VAC BREAKERS ON HBS |