Permit: T05PL00674

Parcel: 131092140


Addresses:

5540 E 26TH ST


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T05PL00674

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/12/2005 PLUMBING - FINAL Approved IVRS - Inspection :*CORRECTION MADE GAS CARD AT METER
04/11/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* READ NOTES FROM 4/8/05 INSPECTION. ROOF CEMENT IS A FLAMMABLE MATERIAL REQUIRING 1" CLEARANCE FROM DOUBLE WALL AND 6" CLEARANCE FROM SINGLE WALL FLUE VENT PIPE. REMOVE AND REPLACE WITH CORRECT VENT ASSEMBLY AT ROOF.
04/08/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :* 14 PSI AIR TEST FROM METER NEW PIPING OVERHEAD TO WATER HEATER,DRYER, AND FURNACE OK. 1) PROVIDE 6" MINIMUM CLEARANCE FROM COMBUSTIBLES ON SINGLE WALL VENT PIPING AND 1" MINIMUM CLEARANCE FROM COMBUSTIBLES ON DOULBE WALL VENT PIPING. 2) PROVIDE 3- GALV SCREWS OR RIVETS AT EACH VENT JOINT CONNECTION. MAKE CORRECTIONS CALL IN FOR INSPECTION FOR GAS CARD.