Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T05PL00674
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/12/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :*CORRECTION MADE GAS CARD AT METER | |
04/11/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* READ NOTES FROM 4/8/05 INSPECTION. ROOF CEMENT IS A FLAMMABLE MATERIAL REQUIRING 1" CLEARANCE FROM DOUBLE WALL AND 6" CLEARANCE FROM SINGLE WALL FLUE VENT PIPE. REMOVE AND REPLACE WITH CORRECT VENT ASSEMBLY AT ROOF. |
|
04/08/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 14 PSI AIR TEST FROM METER NEW PIPING OVERHEAD TO WATER HEATER,DRYER, AND FURNACE OK. 1) PROVIDE 6" MINIMUM CLEARANCE FROM COMBUSTIBLES ON SINGLE WALL VENT PIPING AND 1" MINIMUM CLEARANCE FROM COMBUSTIBLES ON DOULBE WALL VENT PIPING. 2) PROVIDE 3- GALV SCREWS OR RIVETS AT EACH VENT JOINT CONNECTION. MAKE CORRECTIONS CALL IN FOR INSPECTION FOR GAS CARD. |