Permit: T05PL00649

Parcel: 11708017B


Addresses:

428 E 18TH ST


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T05PL00649

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
04/08/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*1) GAS PRESSURE TEST IS OK. 2) ALL CORRECTIONS HAVE BEEN MADE 3) WALL HTR HAS BEEN INSTALLED AS PER INSTALLATION STANDARDS
04/06/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) SHALL LOCATE GAS LINE IN HOUSE TO WALL HTR MIN. 6" ABOVE FLOOR. 2) SHALL PROVIDE FLU VENT & CAP FOR WATER HTR AND TERMINATE MIN. 2" ABOVE ROOF WITH PROPER CLEARANCES. 3) SHALL HARD? PIPE INTO WATER HTR ENCLOSURE THEN LOCATE VAVLE & FLEX CONNECTOR. 4) SHALL PROVIDE 2- 10X10 LOUVER GRILLS LOCATED 12" ABOVE FLOOR AND 12" BELOW CEILING @ WATER HTR ENCLOSURE. 5) SHALL HAVE AIR TEST @ TIME OF INSPECTION.