Permit: T05PL00646

Parcel: 120020480


Addresses:

750 W PRESIDENT ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
05/11/2005 PLUMBING - GAS PRESSURE TEST Approved 1) GAS PRESSURE TEST IS OK. 2) GAS SHUT OFF VALVES OK. 3) NOTE: SHALL CALL FOR FINAL INSPECTION WHEN THE T & P VALVE FOR WATER HTR HAS BEEN REPLACES. 4) SHALL USE C-PVC MATERIAL NOT PVC SCH.40 FOR T & P DRAIN. 5) OK TO BACKFILL TRENCH.
04/12/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) SHALL PROVIDE AN AIR PRESSURE TEST ON ENTIRE SYSTEM MIN OF 10 LBS @ TIME OF NEXT INSPECTION. 2) SHALL HARD PIPE OUT OF HOUSING OF FURNACE THEN CONNECT THE FLEX CONNECTOR. 3) SHALL EXTEND T & P DRAIN @ WATER HTR AND TERMINATE MIN. OF 6" ABOVE GALVANIZED PIPE WITH NO THREADS @ END OF PIPE. 4) SHALL PROVIDE A WATER HEATER ENCLOSURE FOR ANY EXTERIOR LOCATED WATER HEATERS AND DO NOT HAVE THE FLEX CONNECTOR PENETRATE THRU THE ENCLOSURE.