Permit: T05PL00605

Parcel: 137052360


Addresses:

817 W IOWA ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
04/21/2005 PLUMBING - GAS PRESSURE TEST Approved T & P, BOND WIRE, VENT CLEARNACE
04/20/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :* 12 PSI AIR TEST FROM METER NOW PG UNDERGROUND TO BUILDING THRU SERVICE VALVE TO WATER HEATER, FURNACE, STOVE & DRYER OK. 1) WATER HEATER T & TO GRAVITY DRAIN TO DAYLIGHT 2) PROVIDE 1" CLEARANCE FROM COMBUSTIBLES AT VENT FROM WATER HEATERS & FURNACE. 3) PROVIDE BONDING OF BUILDING GAS PIPING.
04/18/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
04/05/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999* PROVIDE MINIMUM 10 PSI TEST AT TIME OF INSPECTION WITH NO PRESSURE DROP FOR 15 MINUTES MINIMUM
04/04/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999* NO ONE HOME