Inspection Status: Approved
Inspection History: SITE - SEWER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/27/2006 | SITE - SEWER | Approved | IVRS - Inspection :* 03055, 03035, 03040 THIS WORK NOT FOR THIS PERMIT - WILL BE SEEN AT EACH BUILDING BUILD OUT 03057 - P.D.E.Q DISCHARGE AUTHORIZATION TURNED IN |
|
| 06/08/2005 | SITE - SEWER | Partial Approval | IVRS - Inspection :* MANHOLE # 19 VACUUM TEST OK. 20 SEC 2/10 DROP. MANHOLE # 20 VACUUM TEST OK. 20 SEC NO DROP. MANHOLE # 16 VACUUM TEST OK. 18SEC NO DROP. MANHOLE # 15 VACUUM TEST OK. 15 SEC NO DROP. MANHOLE # 17 VACUUM TEST OK.18 SEC 3/10 DROP. MANHOLE # 6 VACUUM TEST OK. 11 SEC NO DROP. MANHOLE # 9 VACUUM TEST OK. 13 SEC NO DROP. MANHOLE # 10 VACUUM TEST OK. 11 SEC NO DROP. |
|
| 05/31/2005 | SITE - SEWER | Partial Approval | IVRS - Inspection :* MANHOLE #13 VACUUM TEST OK. MANHOLE # 16 NOT READY. MANHOLE #15 NOT READY. MANHOLE #17 NOT READY | |
| 05/12/2005 | SITE - SEWER | Partial Approval | IVRS - Inspection :* VACUUM TEST ON MAN HOLE 11, 12,18 VACUUM TEST OK. VACUUM TEST 10,15 NOT READY PLEASE MAKE REPAIRS & CALL AGAIN. | |
| 05/11/2005 | SITE - SEWER | Partial Approval | IVRS - Inspection :* VACUUM TEST ON MAN HOLES #4,#3, #2,#1, #7, #8. TEST OK | |
| 05/10/2005 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* NOBODY AROUND TO VACUUM TEST MH | |
| 05/09/2005 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* | |
| 05/03/2005 | SITE - SEWER | Partial Approval | IVRS - Inspection :* | |
| 05/02/2005 | SITE - SEWER | Partial Approval | IVRS - Inspection :* | |
| 04/28/2005 | SITE - SEWER | Partial Approval | IVRS - Inspection :* | |
| 04/27/2005 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 1) TEST OK FROM M-H #1 TO EXISTING TEST ON 8" 2) TEST OK FROM M-H #2 TO M-H #1 TEST OK 3) TEST OK FROM M-H #2 TO M-H #3 8" 4) TEST OK FROM M-H #3 TO M-H #4 8" 5) TEST OK FROM M-H #3 TO 160' 6" LOT #58 |
|
| 04/25/2005 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 1) 6" HCS HAS BEEN INSTALLED FOR LOT #39 AS PER PLAN FROM EXISTING M-H 6597-14. TO M-H #19 TO M-H #20 AND ALS HCS 2) NOTE: INSTALL DIP AT LOTS 32-33 OR PROVIDE A REVISED PLAN |
|
| 04/21/2005 | SITE - SEWER | Partial Approval | IVRS - Inspection :* HCS HAVE BEEN INSTALLED BETWEEN M-H # 6597-13 & M-H #16 | |
| 04/20/2005 | SITE - SEWER | Partial Approval | IVRS - Inspection :* | |
| 04/19/2005 | SITE - SEWER | Partial Approval | IVRS - Inspection :* | |
| 04/18/2005 | SITE - SEWER | Partial Approval | IVRS - Inspection :* DIP FROM M-H #6 PLEASE PROVIDE INFO ON TRANSMISSION BANDS FROM DIP SDR 35 SEE REQUEST 4/5/05. FROM M-H 17-HCS DIP-OK | |
| 04/15/2005 | SITE - SEWER | Partial Approval | IVRS - Inspection :* FROM M-H #8 TO M-H #7 FROM M-H # 7 TO M-H #6 DIP FROM M-H #6 NOT READY. FROM M-H #8 TO M-H # 17 OK. ALSO HCS OK BETWEEN M-H # 7 & #6 OK | |
| 04/14/2005 | SITE - SEWER | Partial Approval | IVRS - Inspection :* PLEASE NOTE WILL REQUIRE VERIFICATION OF GRADE ON SEWER & ITS BRANCHES ALSO VACUUM TEST ON ALL MANHOLES. LOW PRESSURE AIR TEST ALL CO UP TO GRADE. CERTIFICATE OF COMPLETRION FROM DEQ AT TIME OF FINA. ALSO WILL NEED DETAIL OF PROPER INSTILLATION FO TRANSISSION BETWEEN DEP AND SDR 35. 4" HCS FROM M-H # 10 OK. ALSO HCS BETWEEN M-H #9 & M-H #8 OK SUBJECT TO ABOVE. | |
| 04/13/2005 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* | |
| 04/12/2005 | SITE - SEWER | Partial Approval | IVRS - Inspection :* HCS FOR TRUNK LINE BETWEEN M-H #12 & M-H # 11. ALSO HCS INSTALLED IN TRUNK LINE FROM M-H#11 TO M-H #10 | |
| 04/11/2005 | SITE - SEWER | Partial Approval | IVRS - Inspection :* | |
| 04/08/2005 | SITE - SEWER | Partial Approval | IVRS - Inspection :* FROM M-H # 11-TO M-H # 10 TRUNK ONLY WILL NEED TO COMPLETE HCS-CONTRACTOR WILL PROVIDE VERIFICATION OF GRADE LOW PRESSURE AIR TEST & VACUUM TEST AT LATER-ALSO SE OTHER NOTES | |
| 04/07/2005 | SITE - SEWER | Partial Approval | IVRS - Inspection :* FROM 14-TO M-H #13 TO M-H #12 TO M-H#12. TRUNK LINE ONLY-WILL INSTALL HCS AT LATER DATE. | |
| 04/06/2005 | SITE - SEWER | Partial Approval | IVRS - Inspection :* 1) PLEASE PROVIDE THE STANDARD ENGINEERING DETAIL ON THE PROPER INSTALLATION OF STANDARD DUCTILE HCS CONNECTION FROM SDR-35-DUCTILE IRON PIPE MATERIALS. ALSO PROVIDE SPEC ON DIP ? CLASS NOT ON PLAN ? SEAL. PLEASE PROVIDE LISTING ON ? BAN USED FROM SDR-35-DIP 3) ALL HCS CONNECTIONS HAVE BEEN INSTALLED ON SEWER LINE A-WILL NEED ABOVE INFO BEFORE APPROVAL IS GIVEN CONTRACTOR WILL PROVIDE AIR TEST VACUUM TEST AND VERIFICATION OF GRADE AT LATER DATE |
|
| 04/05/2005 | SITE - SEWER | Partial Approval | IVRS - Inspection :* TRUNK LIVE ONLY FROM M-H #2 TO M-H # 3 7 FROM M-H #3 TO MH #4 6" LINE FROM M-H #3 TO END OF RUN WITH TWO WAY C.O CONTRACTOR WILL TEST AT LATE DATE. PLEASE NOTE WILL NEED TO KNOW WHAT TIYPE OF TRANSMISSION TO BE USED FROM SDR 35-DIP-ALSO CLASS OF DIP NOT ON SPEC. | |
| 04/01/2005 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* 8" FROM EXISTING M-H TO M-H #1 OK FROM M-H #1 TO M-H #2 8" OK. OK TO BACKFILL CONTRACTOR WILL PROVIDE VARIFICATION OF GRADE & LOW PRESSURE TEST AT LATER DATE. ALSO WILL REQUIRE VACUUM TEST ON MANHOLES. NEED TO COMPLETE HCS FOR LOTS 9 & 10 | |
| 03/30/2005 | SITE - SEWER | Not ready for Inspection | IVRS - Inspection :* INFO ONLY |