Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/30/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 04/08/2005 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* APPEAL ON JOB CASE # 2005-167. ALSO AN APPROVED PLAN ON JOB WITH GAS LINE IN EASEMENT APPROVED BY PERMIT SPECIALIST DAVE WITT & INSTALLED AS PER APPROVED PLAN. TEST OK OK TO BACKFILL CALL GAS CO 889-1888. CARD LEFT AT METER SET | |
| 03/30/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHALL PROVIDE AN APPROVED PLOT PLAN SHOWING LOCATION OF NEW GAS LINE VERIFICATION THAT THIS NEW LINE IS IN THE PROPERTY NOT EASEMENT RIGHT OF WAY 2) CANNOT HAVE A UNION IN LINE WITHOUT AN APPROVED GAS SHUT OFF VALVE. 3) SHALL EXTEND FURNACE & WATER HTR FLU VENT AND TERMINATE 3'-0" ABOVE COOLER. 4) SHALL EXTEND AND TERMINATE T & P DRAIN FOR WATER HTR TO DAYLIGHT OR PROVIDE APPEAL FORM FOR ALTERNATE METHOD OF T & P INSTALLATION. 5) SHALL PROVIDE REQUIRED TEST GAGE. |