Permit: T05PL00455

Parcel: 119223510


Addresses:

2026 W SAXONY RD

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
03/31/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :* 1) GAS PRESSURE TEST IS OK. 2) GAS SHUT OFF VALVES OK. 3) ALL CORRECTIONS HAVE BEEN MADE.
03/22/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) SHALL REMOVE UNION IN LINE AND REPLACE WITH A RIGHT & LEFT HAND NIPPLE OR LOCATE A SHUT OFF VALVE BEFORE THE UNION. 2) RE TEST THE SYSTEM. 3) CANNOT USE BLK PIPE ON T & P DRAIN AND CUT OFF THREADS @ END OF DRAIN.
03/14/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) SHALL PROVIDE TEST GAGE WITH 1/ 10 INCREMENTS AND SYSTEM PUMPED UP TO 10 LBS MIN @ TIME OF INSPECTION. 2) SHALL REPLACE WATER HTR SHUT OFF VALVE WITH A AGA OR CSA VALVE. 3) SHALL EXTEND WATER HTR FLU VENT 3' 00" ABOVE COOLER WHEN VENT IS LOATED WITHIN 10' OF COOLER. 4) SHALL EXTEND FURNACE FLU VENT 2'-0" ABOVE COOLER. 5) SHALL EXTEND & TERMINATE WATER HTR T & P DRAIN TO DAYLIGHT WITHOUT FLEX LINE AND GRAVITY PITCH.